Rank HTHP

HTHP technology

RANK ® HTHP use low temperature heat sources (25-125ºC) and, with electricity consumption, upgrade temperature (up to 150ºC) and power (500 kWt), with high COP and possibility to cooling and heating simultaneous production.

Own designed high temperature compressor, selected working fluids health and environmentally safety, non-explosive and non-flammable and control software for operation and predictive maintenance management allow us to offer a compact, reliable and long lifespan plug&play solution.

HTHP Water-Water

T out (°C)
Qout = 500kWt COP H+C
150
3,7 4,9 6,0 9,6 12,8
135
3,9 5,5 6,8 12,0 13,8
120
4,3 6,4 9,2 14,8
-
105
5,1 7,4 10,7 15,9
-
90
5,5 10,1 15,3
-
-
T in (°C)
25
50
75
100
125

HTHP Water-Steam

T out (°C)
Qout = 500kWt COP H+C
150
-
-
4,7 6,1 10,2
140
-
3,8 5,8 8,0 10,5
130
3,0 4,7 6,4 9,6 12,2
120
3,6 5,7 8,3 10,1
-
110
4,4 6,2 10,9 13,4
-
T in (°C)
40
60
80
100
120

This content is blocked because YouTube cookies have not been accepted.

Heat Pump Options (HTHP)

Basic

Enclosure

Container

Container +
Steam generation